View Categories

85012M01 | HDR 60W 24V 2.5A Spec

Series: HDR
Version: V1.0
Manufacturer: TILLUME

1. HDR 24V 2.5A 60W Power Supply #

HDR60 24V 2.5A

HDR-60 is an economical ultra-thin 60W rail-type power supply that complies with German industrial standards. It is suitable for installation on TS-35/7.5 or TS-35/15 rails. The body is designed to be 52.5mm (3SU) wide in the cabinet to save space. The entire series uses a full range of AC input from 100VAC to 265VAC.

HDR-60 is designed with a plastic shell, which can effectively prevent users from electrical hazards. The working efficiency is as high as 90%. The entire series can work in an ambient temperature of -20°C to 40°C under air circulation conditions. It has complete protection functions and complies with home automation, making HDR-60 a very competitive home power solution.

2. Electrical Specifications #

Output #

MODELRated Value Note1
DC Voltage24V DC
Rated Current2.5A
Rated Power60W
Ripple & Noise (max) Note260mVp-p/115Vac, 70mVp-p/230Vac
Voltage ADJ. Range23-27.5V
Voltage Tolerance±1.0%
Line Regulation±0.15%
Load Regulation±1.0%
Set Up, Hold up Time350ms, 60ms@230VAC 810ms, 15ms@115VAC at full load

Input #

MODELRated Value
Input Voltage Range100 ~ 265V AC
Frequency Range47 ~ 63 Hz
Efficiency (typ.)92%
Standby power70mW/115Vac, 100mW/230Vac
AC Current (typ.)1.1A/115Vac, 0.6A/230Vac
Inrush Current (typ.)Cold Start 35A/115Vac, 70A/230Vac
  • Note1: Unless otherwise specified, all specifications are measured at 230VAC input, rated load, and 25°C ambient temperature.
  • Note2: Ripple and noise measurement method: Use a 12″ twisted pair cable with 0.1 and 47 capacitors connected in parallel at the terminals and measure at 20MHz bandwidth

Protection #

Over Load #

Output VoltageData Note3
24V3.5A
25V3.4A
26V3.2A
27V3.1A
  • Note3 : Test conditions: Ambient temperature 25°C, test after 2 hours of full load operation.
  • Note4 : When Enter Over Load Protection, System entering hiccup mode, it can automatically recover after the abnormal load condition is removed
MODELData
Over Voltage Note527.4-28V
Short Current ProtectionYes
  • Note5 : System entering hiccup mode, it can automatically recover after the abnormal load condition is removed

3.Mechanical Structure #

Physical Parameters #

ParameterData
Housing MaterialABS
Adapter RailCTS-35/7.5 or TS-35/15
IP GradeIP20
Dimension52.5*90*58mm(W*H*D)
Weight165g

Terminal Pin Definition #

Pin No.Pin Function
1AC / L
2AC / N
3, 4V+
5, 6V-
TILLUME HDR60 Size

4. Environmental Adaptability #

ParameterData
Work Temperature-25℃ ~ +60℃
Storage Temperature-25℃ ~ +80℃
Humidity45%-75% RH
Lifespan>50,000hrs @Ta=25℃

5. Conformity List #

EMC Directive Related Standards​Test Level
EN 55032 / ConductedClass B
EN 55032 / RadiatedClass B
​EN 61000-3-2 / Harmonic CurrentClass A.
​EN 61000-4-2 / ESDLevel 3
​EN 61000-4-3 / Radiated SusceptibilityLevel 3
EN 61000-4-4 / EFT. BurestLevel 3
EN 61000-4-5 / SurgeLevel 4
EN 61000-4-6 / ConductedLevel 3
EN 61000-4-8 / Magnetic FieldLevel 4
EN 61000-4-11 / Voltage Dips and interruptions>95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods